TDS-NC1200-HI / Rev. A  ·  Issue: October 2026

IAS-NC1200-HI
Nuclear Air Purification Cart

IAS-NC1200-HI nuclear air purification carts — vertical cabinets showing differential pressure gauge, fan control and status indicator lamps (photographed units carry the China-market JJH-2000 nameplate — same product)
IAS-NC1200-HI Nuclear Air Purification Cart (China-market nameplate: JJH-2000) — Differential Pressure Gauge · Fan Control · Status Indicators · Caster-Mounted

Mobile nuclear air cleaning cart for decommissioning, radiological maintenance outages, waste handling and local-space contamination control. 2,000 m³/h class with VFD blower speed control, in the EJ/T 20088-2014 portable cart configuration. Sold in China as the JJH-2000 — same product, regional model name (how our model numbers work).

2,000m³/h
Rated Airflow
1,180CFM
Rated Airflow (Imperial)
VFDDrive
Adjustable Blower Speed
ΔPGauge
Built-In Filter Monitoring
The NC Series

The Cart Family on the Production Floor

The IAS-NC1200-HI belongs to the NC-series nuclear air purification cart family. This short walk past the production lineup shows its sister units — the IAS-NC1800-HI and IAS-NC300-HI (filmed units carry their China-market JJH-3000 / JJH-500 nameplates) — with the same design language: front-panel differential pressure gauges, VFD controls and caster-mounted cabinets.

Section 4 — Technical Data

Technical Specifications

Configuration: vertical caster-mounted cart for local-space nuclear air cleaning, with VFD-controlled blower and front-panel differential pressure monitoring. Filtration train, stage efficiencies and test documentation are issued with the project data sheet for each order.

ParameterValue
4.1 General Specifications
ModelIAS-NC1200-HI (China-market designation: JJH-2000 — same product)
Equipment ClassPortable nuclear air purification cart (local-space, in-cell air cleaning)
Rated Airflow2,000 m³/h (≈ 1,180 CFM)
Blower ControlVFD adjustable speed drive — airflow set and trimmed from the front panel to hold the enclosure at the required negative pressure
Filtration TrainNuclear air cleaning train in the EJ/T 20088-2014 cart configuration — aerosol HEPA stage + impregnated activated-carbon iodine adsorber stage; stage efficiencies and test data issued with the project data sheet
MonitoringBuilt-in differential pressure gauge on the front panel — filter loading read at a glance, no external instrument needed
ControlsFan switch + run / status indicator lamps on the front panel
Housing / ConstructionPowder-coated steel cabinet, high-visibility orange — vertical configuration, compact footprint
MobilityHeavy-duty casters — roll into position at the work enclosure, lock in place for operation
Design StandardEJ/T 20088-2014 (portable, local-space nuclear air cleaning carts)
4.2 Project-Specific Data — Issued With Each Order
Electrical SupplyConfirmed at order (voltage / phase / frequency matched to destination)
Overall DimensionsIssued with the project data sheet
WeightIssued with the project data sheet
Filter Replacement CriteriaDifferential pressure trigger per the project data sheet (commonly ≈ 2× clean resistance); dose-rate criteria per facility radiological protection procedures
Section 3 — Design

Design Advantages

Variable Frequency Drive (VFD) Blower Control

Airflow is dialed in from the front panel and trimmed as filters load, so the work enclosure stays at its specified negative pressure across the whole filter life — no damper changes, no mechanical modification.

Built-In Differential Pressure Gauge

The front-panel ΔP gauge shows filter loading continuously. Operators see at a glance when a stage is approaching its change-out point and can plan the swap into the outage schedule instead of reacting to it.

Caster-Mounted Vertical Cabinet

A compact vertical footprint on heavy-duty casters: the cart rolls through standard doorways to the enclosure, positions where the work is, and locks in place. No skid, no crane, no fixed installation.

Front-Panel Controls & Status Indicators

Fan switch and run / status indicator lamps are grouped on the front panel with the pressure gauge — one face for start-up, speed adjustment and routine checks during operation.

High-Visibility Safety Finish

The orange powder-coated cabinet stays visible in congested decommissioning work zones, and the coated steel surface wipes down for contamination control between deployments.

Section 5 — Consumables

Replacement Filter Components & Consumables

Replacement elements for the IAS-NC1200-HI — HEPA aerosol elements, iodine (activated carbon) adsorber elements and pre-filters — are supplied by part number against the project data sheet issued with your unit. See the nuclear consumables catalogue or contact sales@iodineairsystems.com with your unit's data sheet reference for restocking.

Section 6 — Operation

Installation & Operation

6.1

Positioning & Connection

  • Roll the cart into position at the work enclosure and lock the casters.
  • Connect inlet / outlet ducting to the enclosure per the project layout, and confirm airflow direction before start-up.
  • Confirm each filter element is seated and the access panels are fully closed before placing the unit in service.
6.2

Start-Up Procedure

  • Connect the unit to the facility supply specified on the nameplate / project electrical data. The power indicator lamp illuminates when energized.
  • Start the fan from the front-panel switch, then raise blower speed gradually on the VFD control to the required airflow.
  • Verify the enclosure has reached its specified negative pressure before work begins.
CAUTION: Adjust blower speed gradually. Abrupt speed changes may cause airflow transients that disrupt enclosure negative pressure.
6.3

Routine Use

  • Read the differential pressure gauge each shift. Plan filter change-out when the reading approaches the trigger value in the project data sheet.
  • Trim blower speed on the VFD as filters load, to hold enclosure negative pressure without over-ventilating.
  • Schedule periodic on-site inspection per facility radiological protection procedures.
6.4

Filter Removal

  • Wear appropriate protective gloves and PPE before servicing filters.
  • Stop the unit and isolate power before opening the filter access panels.
  • Double-bag removed filter elements in sealed plastic immediately upon removal.
  • Handle and dispose of filters per facility radiological waste management procedures.
Section 8 — Ordering

Ordering Information

Model Code: IAS – NC – 1200 – HI

IASIodine Air Systems (brand)
NCNuclear Cart — portable local-space nuclear air cleaning cart
1200Nominal airflow class 1,200 CFM (rated 2,000 m³/h)
HIHEPA + Iodine (activated carbon) adsorber configuration
CUSTOMOEM configuration built to customer requirements (see below)
Part NumberDescription
IAS-NC1200-HIComplete unit — nuclear air purification cart, 2,000 m³/h (≈1,180 CFM), VFD blower, built-in ΔP gauge, caster-mounted
IAS-NC1200-HI-CUSTOMOEM configuration — built to customer requirements: filtration configuration, electrical supply, housing material and finish, and customer branding, confirmed in the quotation
Replacement elementsHEPA / iodine adsorber / pre-filter elements — by project data sheet
DocumentationProject data sheet; test reports as specified in the quotation

Pricing, lead time and freight (FOB / CIF) are confirmed in the written quotation. Contact sales@iodineairsystems.com or with your airflow, enclosure and documentation requirements.