Data Center Air Filtration
Prefilter to Gas-Phase

Pleated panel prefilters, rigid-box and V-bank final filters, critical-zone HEPA, and gas-phase/carbon filters for corrosion control — a standard-size line built around the 24×24 in. nominal filter-wall opening common to data center AHUs and filter banks.

ASHRAE 52.2 ISO 16890 EN 1822:2009 (critical zones) UL 900
2,000CFM
Per-filter airflow class
8–15MERV
Prefilter to final-filter range
H14target
Critical-zone HEPA design point
G1target
Gas-phase corrosion control (ISA-71.04)
The Challenge

What Data Centers Demand From Air Filtration

Outdoor air brings particulate and gaseous contamination into a data center's air stream. ASHRAE Technical Committee 9.9 publishes specific filtration guidance to protect IT hardware reliability.

🌫️

Particulate Ingress & IT Reliability

ASHRAE TC9.9's own guidance: room air may be continuously filtered with MERV 8 filters, and air entering the data center with MERV 11, or preferably MERV 13, filters — targeting ISO 14644-1 Class 8 cleanliness.

🧪

Corrosive Gases

Sulfur-bearing and other corrosive gases (H₂S, SO₂, Cl₂, NOₓ, NH₃, HF, ozone) drive copper creep corrosion and silver-sulfide failures on circuit boards. ASHRAE TC9.9 recommends holding the environment within ISA-71.04 severity level G1.

❄️

Coil & Downstream Fouling

A MERV 8 pleated prefilter ahead of a finer final filter protects cooling coils and extends final-filter life by capturing coarse dust before it loads the finer media.

🏗️

Standard 24×24 Openings

AHU and filter-wall-bank openings in data centers are generally built around the 24×24 in. nominal filter face, so a consistent part line across prefilter, final-filter, HEPA and gas-phase stages simplifies stocking and changeout.

🔁

Scheduled Changeout

Each filter class has a manufacturer-published recommended final (changeout) resistance. Tracking differential pressure against that published figure keeps changeout timing predictable.

📋

Traceable Specifications

Every dimensional and performance figure on an IAS data center filter traces to a named manufacturer reference product. Full detail is confirmed in writing at quotation.

Products

Data Center Air Filtration Product Line

Five filter classes spanning the full stage sequence — pleated prefilter, rigid-box final filter, V-bank final filter, critical-zone HEPA, and gas-phase/carbon for corrosion control.

IAS-DC-PANEL-2424
Pleated Panel Prefilter, MERV 8

First-stage prefilter for outdoor-air intake and makeup-air units. Protects cooling coils and extends the life of downstream final filters by capturing coarse dust and insects ahead of the finer media.

24×24×2 & 24×24×4 in. 2,000 cfm 0.31 / 0.27 in. w.g. initial ASHRAE 52.2 UL 900
Full Technical Data Sheet
IAS-DC-RIGID-2424
Rigid Box Final Filter, MERV 13/14

Second-stage final filter for data center AHUs and filter-wall banks — the MERV 13-14 range ASHRAE TC9.9 names as the preferred filtration for air entering a data center.

24×24×12 in. 2,000 cfm 0.60 / 0.65 in. w.g. initial ASHRAE 52.2 UL 900
Full Technical Data Sheet
IAS-DC-VBANK-2424
V-Bank Final Filter, MERV 14/15

Mini-pleat V-bank final filter for sites that want more media area and lower face-area pressure drop than a rigid box at the same MERV grade. Same 24×24×12 in. envelope as the rigid-box filter.

24×24×12 in. 2,000 cfm 0.29–0.51 in. w.g. initial ASHRAE 52.2 UL 900
Full Technical Data Sheet
IAS-DC-HEPA-2424
Data Center HEPA Filter, H14 Design Target

Deep-pleat HEPA for critical-zone data center air handling — cleanroom-adjacent server halls or customer specifications calling for HEPA-level filtration upstream of the cooling coil. Shares its 24×24×11.5 in. envelope with our nuclear-grade IAS-HEPA-2424-B-SS.

24×24×11.5 in.~2,000 cfm≤1.4 in. w.g. initialEN 1822 H14 design target
Full Technical Data Sheet
IAS-DC-GASPHASE
Gas-Phase / Carbon Filter for Corrosion Control

V-cell activated-carbon / chemisorbent filter for sites at risk of exceeding ISA-71.04 severity level G1 — the corrosive-gas target ASHRAE TC9.9 recommends for data centers. Same 24×24×12 in. envelope as the final-filter stages, for straightforward bank staging.

24×24×12 in. 2,000 cfm 0.38 in. w.g. @ 500 fpm G1 (ISA-71.04) design target
Full Technical Data Sheet
Applications

Where These Products Are Used

Outdoor-Air Intake & Makeup-Air Units

A MERV 8 pleated prefilter ahead of a MERV 13-15 final filter is the general-purpose arrangement for outdoor air entering a data center air handling unit, per ASHRAE TC9.9 guidance.

CRAH / CRAC-Adjacent AHU Filter Banks

Room-level recirculation air handling serving CRAH/CRAC-cooled spaces is commonly filtered at MERV 8, per ASHRAE TC9.9's room-air recommendation; CRAH/CRAC cabinets themselves generally take OEM-specific filter sizes mounted directly in the unit, separate from the room-level AHU bank.

Critical-Zone / Cleanroom-Adjacent Server Halls

Where a facility specification calls for HEPA-level filtration — for example a server hall sharing air handling with adjacent cleanroom space — the HEPA stage is added upstream of, not instead of, the particulate final filter.

Corrosion Control at Industrial / Coastal Sites

Sites near industrial, coastal or high-pollution sources are more likely to exceed ISA-71.04 severity level G1. Gas-phase filtration of inlet and/or recirculated air is the control ASHRAE TC9.9 recommends in that situation.

Filter-Wall Bank Changeout Programs

Prefilter, final-filter, HEPA and gas-phase stages each carry their own manufacturer-published recommended final (changeout) resistance — see each product's Technical Data Sheet for the figure that applies to that stage.

Compliance

Standards Referenced

Every figure on the product pages in this section traces to a named manufacturer reference product tested or classified to one of these standards. See each product's Technical Data Sheet, and research.md, for the specific source.

📐

ASHRAE 52.2

Method of testing general ventilation air-cleaning devices for removal efficiency by particle size — the basis for MERV ratings used on the prefilter, rigid-box and V-bank final filters.

🌐

ISO 16890

ePM1 / ePM2.5 / ePM10 efficiency rating referenced alongside MERV by the manufacturer reference products for the prefilter, rigid-box and V-bank final filters.

🏛️

EN 1822:2009

HEPA/ULPA classification by MPPS efficiency (H13 ≥99.95%, H14 ≥99.995%). Used as a design target for the critical-zone HEPA filter; not an independent certification of the IAS product.

🧪

ANSI/ISA-71.04

Corrosive-gas severity classification (G1-GX by copper/silver coupon reactivity). ASHRAE TC9.9 recommends targeting severity level G1 for data centers.

📄

ASHRAE TC9.9 Guidance

Technical Committee 9.9's own published whitepaper recommends MERV 8 room-air / MERV 11-13 entering-air filtration and the ISA-71.04 G1 gaseous-contamination target for data centers.

🔥

UL 900 / UL 586

Flammability/smoke listing (UL 900) referenced by the prefilter, rigid-box and V-bank reference products, and the individual-filter test program (UL 586) referenced for the HEPA product family.

FAQ

Data Center Filtration — Frequently Asked Questions

What MERV rating does a data center need?
ASHRAE Technical Committee 9.9's own guidance states that room air may be continuously filtered with MERV 8 filters, and air entering a data center may be filtered with MERV 11 or preferably MERV 13 filters, to help meet ISO 14644-1 Class 8 cleanliness. Many designs use MERV 8 as a prefilter ahead of a MERV 13-15 final filter rather than either alone.
Do I need HEPA filtration in a data center?
Most data centers do not need HEPA; MERV 13-15 final filtration is the common design point per ASHRAE TC9.9 guidance. HEPA (H13/H14 design target) is used only in critical zones — for example where a server hall is adjacent to cleanroom space, or where a customer's own specification calls for HEPA-level filtration upstream of the cooling coil.
What is "G1" and do I need gas-phase filtration?
G1 is the mildest corrosive-gas severity level under ANSI/ISA-71.04, defined by copper (and, per the same ASHRAE TC9.9 source, silver) coupon reactivity below 300 angstroms per month. ASHRAE TC9.9 recommends data centers stay within G1, and recommends gas-phase filtration where ambient sulfur-bearing or other corrosive gases put a site at risk of exceeding it — for example near industrial, coastal or high-pollution sites.
Are these filters interchangeable with name-brand parts I already use?
Each IAS data center filter is built to the same published dimensional and performance specification as a named manufacturer reference product (see each product's Technical Data Sheet). They are IAS products, not the referenced manufacturer's products, and IAS is not affiliated with any of them. Confirm interchangeability against your own housing and specification before ordering.
What sizes are available?
The prefilter is 24×24×2 in. and 24×24×4 in. The rigid-box, V-bank and gas-phase filters are 24×24×12 in. The HEPA filter is 24×24×11.5 in. All are nominal sizes built around the standard 24×24 in. data center filter-wall opening; other sizes may be available on request — contact sales@iodineairsystems.com.
How do I order?
Email sales@iodineairsystems.com with the part number, quantity, delivery destination, Incoterm (FOB or CIF), and your required date. Pricing and lead time are confirmed in the quotation; Iodine Air Systems does not publish prices.
Why Iodine Air Systems

We Control the Supply Chain — So Your Change-Outs Stay on Schedule

Most data center filtration problems are not product problems. They are supply-chain problems: a frame size quietly discontinued, a media substituted without notice, a shipment that slips past the one maintenance window in the quarter. Iodine Air Systems exists to remove that risk. Specification, sourcing, quality checking and delivery for every filter in this line are managed by one accountable US-based supplier — us — not handed off between brokers.

Specification consistency

Every order and reorder is checked against the same published specification — frame dimensions, media class, rated airflow and initial resistance — so the filter that arrives in year three matches the one you qualified in year one.

Continuity of supply

Because we control the chain end to end, replacement cycles are planned around your maintenance windows, and cross-references are maintained when OEM models change — no last-minute substitutions at the loading dock.

One point of accountability

Quotes, documentation, order status and delivery coordination for prefilters, final filters, HEPA and gas-phase all run through a single contact: sales@iodineairsystems.com.

Request a Data Center Filtration Quote

Email our team with your part numbers, quantities and destination — we confirm specification, documentation and lead time in the quotation.