Pleated panel prefilters, rigid-box and V-bank final filters, critical-zone HEPA, and gas-phase/carbon filters for corrosion control — a standard-size line built around the 24×24 in. nominal filter-wall opening common to data center AHUs and filter banks.
Outdoor air brings particulate and gaseous contamination into a data center's air stream. ASHRAE Technical Committee 9.9 publishes specific filtration guidance to protect IT hardware reliability.
ASHRAE TC9.9's own guidance: room air may be continuously filtered with MERV 8 filters, and air entering the data center with MERV 11, or preferably MERV 13, filters — targeting ISO 14644-1 Class 8 cleanliness.
Sulfur-bearing and other corrosive gases (H₂S, SO₂, Cl₂, NOₓ, NH₃, HF, ozone) drive copper creep corrosion and silver-sulfide failures on circuit boards. ASHRAE TC9.9 recommends holding the environment within ISA-71.04 severity level G1.
A MERV 8 pleated prefilter ahead of a finer final filter protects cooling coils and extends final-filter life by capturing coarse dust before it loads the finer media.
AHU and filter-wall-bank openings in data centers are generally built around the 24×24 in. nominal filter face, so a consistent part line across prefilter, final-filter, HEPA and gas-phase stages simplifies stocking and changeout.
Each filter class has a manufacturer-published recommended final (changeout) resistance. Tracking differential pressure against that published figure keeps changeout timing predictable.
Every dimensional and performance figure on an IAS data center filter traces to a named manufacturer reference product. Full detail is confirmed in writing at quotation.
Five filter classes spanning the full stage sequence — pleated prefilter, rigid-box final filter, V-bank final filter, critical-zone HEPA, and gas-phase/carbon for corrosion control.
First-stage prefilter for outdoor-air intake and makeup-air units. Protects cooling coils and extends the life of downstream final filters by capturing coarse dust and insects ahead of the finer media.
Second-stage final filter for data center AHUs and filter-wall banks — the MERV 13-14 range ASHRAE TC9.9 names as the preferred filtration for air entering a data center.
Mini-pleat V-bank final filter for sites that want more media area and lower face-area pressure drop than a rigid box at the same MERV grade. Same 24×24×12 in. envelope as the rigid-box filter.
Deep-pleat HEPA for critical-zone data center air handling — cleanroom-adjacent server halls or customer specifications calling for HEPA-level filtration upstream of the cooling coil. Shares its 24×24×11.5 in. envelope with our nuclear-grade IAS-HEPA-2424-B-SS.
V-cell activated-carbon / chemisorbent filter for sites at risk of exceeding ISA-71.04 severity level G1 — the corrosive-gas target ASHRAE TC9.9 recommends for data centers. Same 24×24×12 in. envelope as the final-filter stages, for straightforward bank staging.
A MERV 8 pleated prefilter ahead of a MERV 13-15 final filter is the general-purpose arrangement for outdoor air entering a data center air handling unit, per ASHRAE TC9.9 guidance.
Room-level recirculation air handling serving CRAH/CRAC-cooled spaces is commonly filtered at MERV 8, per ASHRAE TC9.9's room-air recommendation; CRAH/CRAC cabinets themselves generally take OEM-specific filter sizes mounted directly in the unit, separate from the room-level AHU bank.
Where a facility specification calls for HEPA-level filtration — for example a server hall sharing air handling with adjacent cleanroom space — the HEPA stage is added upstream of, not instead of, the particulate final filter.
Sites near industrial, coastal or high-pollution sources are more likely to exceed ISA-71.04 severity level G1. Gas-phase filtration of inlet and/or recirculated air is the control ASHRAE TC9.9 recommends in that situation.
Prefilter, final-filter, HEPA and gas-phase stages each carry their own manufacturer-published recommended final (changeout) resistance — see each product's Technical Data Sheet for the figure that applies to that stage.
Every figure on the product pages in this section traces to a named manufacturer reference product tested or classified to one of these standards. See each product's Technical Data Sheet, and research.md, for the specific source.
Method of testing general ventilation air-cleaning devices for removal efficiency by particle size — the basis for MERV ratings used on the prefilter, rigid-box and V-bank final filters.
ePM1 / ePM2.5 / ePM10 efficiency rating referenced alongside MERV by the manufacturer reference products for the prefilter, rigid-box and V-bank final filters.
HEPA/ULPA classification by MPPS efficiency (H13 ≥99.95%, H14 ≥99.995%). Used as a design target for the critical-zone HEPA filter; not an independent certification of the IAS product.
Corrosive-gas severity classification (G1-GX by copper/silver coupon reactivity). ASHRAE TC9.9 recommends targeting severity level G1 for data centers.
Technical Committee 9.9's own published whitepaper recommends MERV 8 room-air / MERV 11-13 entering-air filtration and the ISA-71.04 G1 gaseous-contamination target for data centers.
Flammability/smoke listing (UL 900) referenced by the prefilter, rigid-box and V-bank reference products, and the individual-filter test program (UL 586) referenced for the HEPA product family.
Most data center filtration problems are not product problems. They are supply-chain problems: a frame size quietly discontinued, a media substituted without notice, a shipment that slips past the one maintenance window in the quarter. Iodine Air Systems exists to remove that risk. Specification, sourcing, quality checking and delivery for every filter in this line are managed by one accountable US-based supplier — us — not handed off between brokers.
Every order and reorder is checked against the same published specification — frame dimensions, media class, rated airflow and initial resistance — so the filter that arrives in year three matches the one you qualified in year one.
Because we control the chain end to end, replacement cycles are planned around your maintenance windows, and cross-references are maintained when OEM models change — no last-minute substitutions at the loading dock.
Quotes, documentation, order status and delivery coordination for prefilters, final filters, HEPA and gas-phase all run through a single contact: sales@iodineairsystems.com.