IAS-DC-GASPHASE Gas-Phase / Carbon
Filter for Corrosion Control

Technical Data Sheet — Revision 1.0 · Effective Date: November 2026

2,000 CFM0.38 in. w.g. @ 500 fpm24×24×12 in.G1 (ISA-71.04) design target
Request Quote
2,000
CFM airflow
capacity
0.38
in. w.g. @
500 fpm
1.0
in. carbon
bed thickness
24×24×12
Nominal size
inches
G1
ISA-71.04 design
target
// Product Description

V-Cell Carbon Filter for
Data Center Corrosion Control

IAS-DC-GASPHASE is a loose-fill V-cell activated-carbon cartridge for data center corrosion control. ASHRAE Technical Committee 9.9's own whitepaper recommends holding a data center's gaseous contamination within ISA-71.04 severity level G1, and states that "for data centers with higher gaseous contamination levels, gas-phase filtration of the inlet air and the air in the data center is highly recommended." IAS-DC-GASPHASE targets that recommendation.

The cartridge holds 1 in. molecular-media panels in a galvanized-steel frame with impact-resistant plastic end caps and a 1-in. nominal mounting header, assembled into a V-cell configuration. In the standard 24 × 24 × 12 in. envelope it is rated for 2,000 cfm at 0.38 in. w.g. resistance (500 fpm face velocity).

// Cross-reference

Built to the same published dimensional and performance specification as Camfil CamCarb VC loose-fill V-cell cartridge, model 242412 (24 × 24 × 12 in., 2,000 cfm, 0.38 in. w.g. at 500 fpm). Camfil and CamCarb belong to Camfil; Iodine Air Systems is not affiliated with Camfil. Confirm interchangeability against your housing before ordering.

// What this filter does not claim

IAS-DC-GASPHASE is not tested or certified to any specific percentage removal of any named gas, and does not itself guarantee ISA-71.04 G1 classification at your site — G1 attainment depends on your ambient gas concentrations, airflow, media selection and media life, and is normally confirmed by reactive (copper/silver coupon) monitoring after installation. We will discuss your target gases and site conditions at quotation.

// Construction at a Glance

Media & Frame

// No photograph available

Product photography for IAS-DC-GASPHASE is in preparation. Construction and dimensional detail are fully specified in the table below.

  • Loose-fill molecular media, 1-in. panels: granular/pelletized activated carbon or activated-alumina/potassium-permanganate blends
  • Galvanized-steel frame, impact-resistant plastic end caps
  • V-cell panel configuration
  • 1-in. nominal mounting header for side-access or built-up bank installation
V-cell activated-carbon gas-phase filter seen at an angle, showing black pleated carbon media panels in a V configuration inside a metal frame
V-cell activated-carbon construction in the 24×24×12 in. envelope (illustration). Media blend, frame material and performance for IAS-DC-GASPHASE follow the specification table below, not this illustration.
// Technical Data Sheet

Complete Technical Specifications

IAS-DC-GASPHASE — dimensions, performance and media
ParameterValue (SI / Metric)Value (US Customary)
— Dimensions —
Nominal size24 × 24 × 12 in.
Actual size23.38 × 23.38 × 11.50 in.
Bed thickness1.0 in.
— Performance —
Airflow capacity≈3,400 m³/h2,000 cfm
Resistance at capacity≈95 Pa0.38 in. w.g. at 500 fpm
Minimum media residence time0.026 seconds at 500 fpm
Recommended upstream protectionMinimum MERV 13 particulate filter (controls carbon dusting); optional second particulate filter downstream
— Media —
Media optionsGranular or pelletized activated carbon; activated alumina impregnated with potassium permanganate; acid-gas-targeted carbon/alumina blends
— Design target —
Target classificationANSI/ISA-71.04 severity level G1 — copper and silver coupon reactivity <300 Å/month, per ASHRAE TC9.9 guidance. Design target only; site-specific attainment confirmed by on-site reactive monitoring, not by this data sheet.
— Operating limits —
Max. continuous operating temperature / RH38 °C / 75% RH100 °F / 75% RH

Metric values are conversions of the US customary specification. Specification values are those published for the Camfil CamCarb VC reference product (see cross-reference above). IAS-DC-GASPHASE is not independently tested against any specific gas or ASHRAE 145.2 report; such test reports, if required, are discussed and confirmed at quotation.

// Where it is used

Applications

For the particulate final-filter stage, see IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424, both in the same 24×24×12 in. envelope.

// FAQ

Questions about IAS-DC-GASPHASE

What is ISA-71.04 severity level G1, and does this filter guarantee it?

G1 is the mildest corrosive-gas severity level under ANSI/ISA-71.04. ASHRAE Technical Committee 9.9's 2009 whitepaper defines it as copper and silver coupon reactivity below 300 angstroms per month, and recommends data centers target G1. IAS-DC-GASPHASE is designed toward that target; it does not guarantee G1 classification for any specific site, since actual results depend on your gas concentrations, airflow, media life and site conditions. Reactive monitoring with copper/silver coupons is the standard way to confirm whether a site meets G1.

Do I still need a particulate filter if I install this?

Yes. The manufacturer reference construction recommends a minimum MERV 13 particulate filter installed upstream to protect the carbon bed from dusting, and optionally a second particulate filter downstream to catch any carbon fines. See IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424 for a MERV 13-15 particulate stage.

Which media should I choose?

Granular or pelletized activated carbon targets general VOCs, odors and ozone. Activated alumina impregnated with potassium permanganate (or blended with carbon) targets a wider range of oxidizable and acidic gases, including the sulfur-bearing gases (H2S, SO2) most often implicated in data center corrosion. Tell us your target gases and site conditions when you request a quote and we will confirm the recommended media.

Is IAS-DC-GASPHASE a replacement for Camfil CamCarb VC?

It is built to the same published dimensional and performance specification as Camfil CamCarb VC in 24 × 24 × 12 in.: 2,000 cfm airflow capacity and 0.38 in. w.g. resistance at 500 fpm. It is an Iodine Air Systems product, not a Camfil product, and we are not affiliated with Camfil. Confirm interchangeability against your housing before ordering.

How do I order?

Email sales@iodineairsystems.com with the media type, quantity, delivery destination, Incoterm (FOB or CIF), and your required date. Pricing and lead time are confirmed in the quotation.