IAS-DC-GASPHASE Gas-Phase / Carbon
Filter for Corrosion Control
Technical Data Sheet — Revision 1.0 · Effective Date: November 2026
capacity
500 fpm
bed thickness
inches
target
V-Cell Carbon Filter for
Data Center Corrosion Control
IAS-DC-GASPHASE is a loose-fill V-cell activated-carbon cartridge for data center corrosion control. ASHRAE Technical Committee 9.9's own whitepaper recommends holding a data center's gaseous contamination within ISA-71.04 severity level G1, and states that "for data centers with higher gaseous contamination levels, gas-phase filtration of the inlet air and the air in the data center is highly recommended." IAS-DC-GASPHASE targets that recommendation.
The cartridge holds 1 in. molecular-media panels in a galvanized-steel frame with impact-resistant plastic end caps and a 1-in. nominal mounting header, assembled into a V-cell configuration. In the standard 24 × 24 × 12 in. envelope it is rated for 2,000 cfm at 0.38 in. w.g. resistance (500 fpm face velocity).
Built to the same published dimensional and performance specification as Camfil CamCarb VC loose-fill V-cell cartridge, model 242412 (24 × 24 × 12 in., 2,000 cfm, 0.38 in. w.g. at 500 fpm). Camfil and CamCarb belong to Camfil; Iodine Air Systems is not affiliated with Camfil. Confirm interchangeability against your housing before ordering.
IAS-DC-GASPHASE is not tested or certified to any specific percentage removal of any named gas, and does not itself guarantee ISA-71.04 G1 classification at your site — G1 attainment depends on your ambient gas concentrations, airflow, media selection and media life, and is normally confirmed by reactive (copper/silver coupon) monitoring after installation. We will discuss your target gases and site conditions at quotation.
Media & Frame
Product photography for IAS-DC-GASPHASE is in preparation. Construction and dimensional detail are fully specified in the table below.
- Loose-fill molecular media, 1-in. panels: granular/pelletized activated carbon or activated-alumina/potassium-permanganate blends
- Galvanized-steel frame, impact-resistant plastic end caps
- V-cell panel configuration
- 1-in. nominal mounting header for side-access or built-up bank installation

Complete Technical Specifications
| Parameter | Value (SI / Metric) | Value (US Customary) |
|---|---|---|
| — Dimensions — | ||
| Nominal size | 24 × 24 × 12 in. | |
| Actual size | 23.38 × 23.38 × 11.50 in. | |
| Bed thickness | 1.0 in. | |
| — Performance — | ||
| Airflow capacity | ≈3,400 m³/h | 2,000 cfm |
| Resistance at capacity | ≈95 Pa | 0.38 in. w.g. at 500 fpm |
| Minimum media residence time | 0.026 seconds at 500 fpm | |
| Recommended upstream protection | Minimum MERV 13 particulate filter (controls carbon dusting); optional second particulate filter downstream | |
| — Media — | ||
| Media options | Granular or pelletized activated carbon; activated alumina impregnated with potassium permanganate; acid-gas-targeted carbon/alumina blends | |
| — Design target — | ||
| Target classification | ANSI/ISA-71.04 severity level G1 — copper and silver coupon reactivity <300 Å/month, per ASHRAE TC9.9 guidance. Design target only; site-specific attainment confirmed by on-site reactive monitoring, not by this data sheet. | |
| — Operating limits — | ||
| Max. continuous operating temperature / RH | 38 °C / 75% RH | 100 °F / 75% RH |
Metric values are conversions of the US customary specification. Specification values are those published for the Camfil CamCarb VC reference product (see cross-reference above). IAS-DC-GASPHASE is not independently tested against any specific gas or ASHRAE 145.2 report; such test reports, if required, are discussed and confirmed at quotation.
Applications
- Corrosion control at data centers near industrial, coastal or high-pollution sources
- Inlet-air gas-phase filtration ahead of the server hall, per ASHRAE TC9.9's recommendation for sites outside the G1 target
- Recirculation-air gas-phase filtration to remove contaminants generated inside the data center
- Staged downstream of a MERV 13-15 particulate final filter in the same 24×24×12 in. filter-wall bank
For the particulate final-filter stage, see IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424, both in the same 24×24×12 in. envelope.
Questions about IAS-DC-GASPHASE
What is ISA-71.04 severity level G1, and does this filter guarantee it?
G1 is the mildest corrosive-gas severity level under ANSI/ISA-71.04. ASHRAE Technical Committee 9.9's 2009 whitepaper defines it as copper and silver coupon reactivity below 300 angstroms per month, and recommends data centers target G1. IAS-DC-GASPHASE is designed toward that target; it does not guarantee G1 classification for any specific site, since actual results depend on your gas concentrations, airflow, media life and site conditions. Reactive monitoring with copper/silver coupons is the standard way to confirm whether a site meets G1.
Do I still need a particulate filter if I install this?
Yes. The manufacturer reference construction recommends a minimum MERV 13 particulate filter installed upstream to protect the carbon bed from dusting, and optionally a second particulate filter downstream to catch any carbon fines. See IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424 for a MERV 13-15 particulate stage.
Which media should I choose?
Granular or pelletized activated carbon targets general VOCs, odors and ozone. Activated alumina impregnated with potassium permanganate (or blended with carbon) targets a wider range of oxidizable and acidic gases, including the sulfur-bearing gases (H2S, SO2) most often implicated in data center corrosion. Tell us your target gases and site conditions when you request a quote and we will confirm the recommended media.
Is IAS-DC-GASPHASE a replacement for Camfil CamCarb VC?
It is built to the same published dimensional and performance specification as Camfil CamCarb VC in 24 × 24 × 12 in.: 2,000 cfm airflow capacity and 0.38 in. w.g. resistance at 500 fpm. It is an Iodine Air Systems product, not a Camfil product, and we are not affiliated with Camfil. Confirm interchangeability against your housing before ordering.
How do I order?
Email sales@iodineairsystems.com with the media type, quantity, delivery destination, Incoterm (FOB or CIF), and your required date. Pricing and lead time are confirmed in the quotation.