IAS-DC-HEPA-2424 Data Center
HEPA Filter, H14 Design Target
Technical Data Sheet — Revision 1.0 · Effective Date: November 2026
airflow
@ rated airflow
target
inches
options
Deep-Pleat HEPA for
Critical-Zone Data Centers
IAS-DC-HEPA-2424 is a deep-pleat HEPA filter for data center critical-zone air handling — for example a server hall that shares air handling with adjacent cleanroom space, or a customer specification that calls for HEPA-level filtration upstream of the cooling coil. Most data centers do not need HEPA; ASHRAE TC9.9's own guidance names MERV 13 (or MERV 11) as the preferred grade for air entering a data center. See our rigid box and V-bank final filters for that general-purpose design point.
The media is deep-pleat glass fiber held apart by aluminum separators. In the standard 24 × 24 × 11.5 in. envelope it is rated for 2,000 scfm at up to 1.4 in. w.g. initial resistance. Frame material is confirmed at quotation.
Built to the same published dimensional envelope (24 × 24 × 11.5 in.) and airflow/initial-resistance performance as AAF International's AstroCel I HCX high-capacity HEPA filter (2,000 scfm @ 1.4 in. w.g.), and designed to meet EN 1822:2009 H14 classification criteria as published for the same AstroCel I deep-pleat product family in AAF's EU catalog edition (same 610 × 610 × 292 mm envelope). AstroCel and AAF belong to AAF International; Iodine Air Systems is not affiliated with AAF. IAS-DC-HEPA-2424 is not independently EN 1822 tested or certified — confirm documentation needs at quotation.
This filter shares its 24 × 24 × 11.5 in. envelope with our own IAS-HEPA-2424-B-SS nuclear-grade separatorless HEPA filter, but uses different internal pleat-pack construction (aluminum-separated deep pleat vs. separatorless) and a different test regime (EN 1822 design target vs. MIL-STD-282/ASME N510). The two are not interchangeable without confirming your application's requirements.

Complete Technical Specifications
| Parameter | Value (SI / Metric) | Value (US Customary) |
|---|---|---|
| — Dimensions — | ||
| Nominal size (H × W × D) | 610 × 610 × 292 mm | 24 × 24 × 11.5 in. |
| — Performance (US catalog basis — AstroCel I HCX reference) — | ||
| Rated airflow | ≈3,400 m³/h | 2,000 scfm |
| Maximum initial resistance at rated airflow | 350 Pa | 1.4 in. w.g. |
| Minimum efficiency | 99.97% and 99.99% on 0.3 µm particles — confirmed at quotation | |
| — Design target (EU catalog basis — same product family/envelope) — | ||
| EN 1822:2009 classification | H13 (≥99.95% at MPPS) / H14 (≥99.995% at MPPS) — design target only; not independently certified | |
| Published initial resistance at classification (reference catalog's own nominal airflow, a different basis from the row above) | H13: 250 Pa · H14: 320 Pa | H13: ≈1.00 in. w.g. · H14: ≈1.28 in. w.g. |
| — Media & pack — | ||
| Media | Deep-pleat glass fiber | |
| Separators | Aluminum | |
Metric values are conversions of the US customary specification except where noted. The US-basis row (rated airflow / initial resistance / 0.3 µm efficiency) and the EU-basis row (EN 1822 classification / initial resistance) come from two different regional catalog editions of the same manufacturer's product family and use different nominal-airflow conventions — they are not a single combined test result. IAS-DC-HEPA-2424 is designed to the EN 1822 H14 criteria shown; it is not independently EN 1822 certified. Iodine Air Systems' own factory test reports are confirmed at quotation.
Applications
- Critical-zone data center air handling — server halls adjacent to cleanroom space
- Customer specifications calling for HEPA-level filtration upstream of the cooling coil
- Installed downstream of, not instead of, a MERV 13-15 particulate final filter
For general-purpose data center final filtration (the design point most data centers use instead of HEPA), see IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424.
Questions about IAS-DC-HEPA-2424
Is this the same filter as IAS-HEPA-2424-B-SS?
No. They share the 24 × 24 × 11.5 in. envelope, but IAS-HEPA-2424-B-SS is our nuclear-grade separatorless (Type B) deep-pleat HEPA filter in a 304 stainless casing, tested to MIL-STD-282 or ASME N510. IAS-DC-HEPA-2424 is built to a different manufacturer's deep-pleat construction with aluminum separators, designed to EN 1822 H13/H14 criteria. The two are not interchangeable without confirming your application's requirements.
Is IAS-DC-HEPA-2424 EN 1822 certified?
No. It is designed to meet EN 1822:2009 H14 classification criteria (minimum efficiency ≥99.995% at the most penetrating particle size) as published for the reference manufacturer's product family. IAS-DC-HEPA-2424 is not independently EN 1822 tested or certified. If your order needs a test report or certification, tell us at the time of request and we will confirm what can be arranged.
Is IAS-DC-HEPA-2424 a replacement for AAF AstroCel I HCX?
It is built to the same published dimensional envelope (24 × 24 × 11.5 in.) and airflow/resistance performance as AAF International's AstroCel I HCX high-capacity HEPA filter (2,000 scfm at 1.4 in. w.g. initial resistance). It is an Iodine Air Systems product, not an AAF product, and we are not affiliated with AAF. Confirm interchangeability against your housing before ordering.
Do I need HEPA filtration in my data center?
Most data centers do not; ASHRAE Technical Committee 9.9's own guidance names MERV 13 (or MERV 11) as the preferred filtration for air entering a data center, with MERV 8 for room air. HEPA is used only in critical zones — for example a server hall sharing air handling with adjacent cleanroom space, or where a customer's own specification calls for HEPA upstream of the cooling coil.
How do I order?
Email sales@iodineairsystems.com with the quantity, delivery destination, Incoterm (FOB or CIF), test documentation you need, and your required date. Pricing and lead time are confirmed in the quotation.