Home › Data Center › IAS-DC-VBANK-2424

IAS-DC-VBANK-2424 V-Bank
Final Filter, MERV 14/15

Technical Data Sheet — Revision 1.0 · Effective Date: November 2026

MERV 14/15 · ASHRAE 52.22,000 CFM24×24×12 in.UL 900
Request Quote
2,000
CFM airflow
capacity
0.29 / 0.51
in. w.g. initial
(MERV 14 / 15)
V-bank
Mini-pleat
construction
24×24×12
Nominal size
inches
UL 900
Listed
// Product Description

V-Bank
Final Filter

IAS-DC-VBANK-2424 is a V-bank final filter for data center air handling units in the same 24 × 24 × 12 in. envelope as IAS-DC-RIGID-2424, for sites that want a V-bank's larger media area and correspondingly lower pressure drop per unit of face area. It is normally installed downstream of a MERV 8 pleated prefilter such as IAS-DC-PANEL-2424.

The MERV 14 grade is a true mini-pleat V-bank: microfine glass-fiber media formed into pleats and assembled into V-shaped banks inside an ABS enclosing frame. The MERV 15 grade is built to a different manufacturer's extended-surface rigid-cell construction using synthetic media, in the same 24 × 24 × 12 in. envelope — see the construction note below before ordering MERV 15.

// Cross-reference

Built to the same published dimensional and performance specification as Camfil Durafil ES2 (MERV 14, mini-pleat V-bank) and AAF VariCel RF (MERV 15, extended-surface rigid cell), both 24 × 24 × 12 in. Camfil, Durafil, AAF and VariCel belong to their respective manufacturers; Iodine Air Systems is not affiliated with either. Confirm interchangeability against your housing before ordering.

// Construction note

No manufacturer data sheet we located publishes a discrete initial-resistance figure for a true mini-pleat V-bank at MERV 15 in this exact size — only resistance-vs-face-velocity curves. The MERV 15 figures on this page are instead sourced from a published rigid-cell (non-V-bank) extended-surface filter in the same envelope. If your project specifically requires V-bank construction at MERV 15, say so when you request a quote and we will confirm what can be sourced.

// Construction at a Glance

Media & Frame

// No photograph available

Product photography for IAS-DC-VBANK-2424 is in preparation. Construction and dimensional detail are fully specified in the table below.

  • MERV 14: microfine glass fiber, mini-pleat, assembled into V-banks, ABS enclosing frame with integral 1-in. header
  • MERV 15: synthetic media, extended-surface rigid cell construction (AAF VariCel RF reference) — no further construction detail published by the manufacturer
Mini-pleat V-bank filter seen at an angle, showing white pleated media in V-shaped cells inside a light-gray plastic frame
Mini-pleat V-bank construction in the 24×24×12 in. envelope (illustration). Media grade and frame material for IAS-DC-VBANK-2424 follow the specification table below, not this illustration.
// Technical Data Sheet

Complete Technical Specifications

IAS-DC-VBANK-2424 — dimensions, performance and construction
ParameterMERV 14 (V-bank)MERV 15 (rigid cell)
— Dimensions —
Nominal size24 × 24 in. face, 12 in. nominal depth
Actual dimensions23.3 × 23.3 in., 11.6 in. actual depth23⅜ × 23⅜ × 11½ in.
— Performance —
Airflow capacity2,000 cfm (≈3,400 m³/h)2,000 cfm (≈3,400 m³/h)
Initial resistance0.29 in. w.g. (≈72 Pa)0.51 in. w.g. (≈127 Pa)
Recommended final resistance≤1.50 in. w.g.1.5 in. w.g.
Media area200 sq ft62 sq ft
Efficiency ratingMERV 14 or MERV 15 per ASHRAE 52.2 with Appendix J (MERV‑A)
— Media & construction —
Construction typeMini-pleat V-bankExtended-surface rigid cell
MediaMicrofine glass fiber, 8.5 pleats/in.Synthetic media
— Listing & limits —
ListingUL 900UL Classified (UL 900 / ULC-S111)
Max. operating temperature175 °F (79 °C)200 °F (93 °C) cont. / 220 °F (107 °C) intermittent

Metric values are conversions of the US customary specification. MERV 14 values are those published for the Camfil Durafil ES2 reference product; MERV 15 values are those published for the AAF VariCel RF reference product — see the construction note above. Iodine Air Systems' own factory test reports are confirmed at quotation.

// Where it is used

Applications

For a prefilter stage upstream, see IAS-DC-PANEL-2424. For a rigid-box alternative in the same envelope, see IAS-DC-RIGID-2424.

// FAQ

Questions about IAS-DC-VBANK-2424

Why does the spec table list two different reference products?

No single manufacturer data sheet we could locate publishes both a MERV 14 and a MERV 15 grade with a discrete initial-resistance figure in a true mini-pleat V-bank construction at 24×24×12 in. The MERV 14 figures come from Camfil's Durafil ES2 mini-pleat V-bank filter; the MERV 15 figures come from AAF's VariCel RF extended-surface rigid-cell filter, a different (non-V-bank) construction from a different manufacturer, in the same nominal envelope. Confirm construction details for your MERV 15 order at quotation.

Should I choose MERV 14 or MERV 15?

MERV 14 (Durafil ES2 reference) gives more media area (200 sq ft) at a lower initial resistance (0.29 in. w.g.) than the MERV 15 reference (62 sq ft, 0.51 in. w.g.). ASHRAE TC9.9's own guidance recommends MERV 13 as the preferred grade for air entering a data center; MERV 14 or 15 is chosen where the site's own specification calls for a finer cut.

What is the difference between this and the rigid box filter, IAS-DC-RIGID-2424?

Both are 24×24×12 in. and rated 2,000 cfm. The MERV 14 V-bank reference (Durafil ES2) is a true mini-pleat V-bank with roughly twice the media area of the rigid-box MERV 14 reference (Camfil Aeropac, 105 sq ft) at a lower initial resistance (0.29 in. w.g. vs. 0.65 in. w.g.). Construction style and media area are the main differences; see each product's own specification table.

Is IAS-DC-VBANK-2424 a replacement for Camfil Durafil ES2 or AAF VariCel RF?

It is built to the same published dimensional and performance specification as Camfil Durafil ES2 (MERV 14) and AAF VariCel RF (MERV 15), both in 24×24×12 in. It is an Iodine Air Systems product, not a Camfil or AAF product, and we are not affiliated with either. Confirm interchangeability against your housing before ordering.

How do I order?

Email sales@iodineairsystems.com with the part number (MERV grade), quantity, delivery destination, Incoterm (FOB or CIF), and your required date. Pricing and lead time are confirmed in the quotation.

Request a quote for IAS-DC-VBANK-2424