IAS-DC-PANEL-2424 Pleated Panel
Prefilter, MERV 8
Technical Data Sheet — Revision 1.0 · Effective Date: November 2026
capacity
(2 in. / 4 in.)
w/ Appendix J
inches
Data Center
Pleated Panel Prefilter
IAS-DC-PANEL-2424 is a medium-efficiency pleated panel prefilter for data center outdoor-air intake, makeup-air units and general-purpose air handling. It is the first filtration stage ASHRAE Technical Committee 9.9's own published guidance describes for data center room air, and is normally staged ahead of a MERV 13-15 final filter such as IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424 on outdoor-air intake.
The media is a synthetic polyester blend formed into a uniform radial pleat, backed by a welded-wire support grid, in a high wet-strength beverage-board frame. Available in two depths — 2 in. and 4 in. nominal — both rated for 2,000 cfm in the 24 × 24 in. face.
Built to the same published dimensional and performance specification as Camfil Farr 30/30 (24 × 24 × 2 in. and 24 × 24 × 4 in., MERV 8). Camfil and Farr 30/30 belong to Camfil; Iodine Air Systems is not affiliated with Camfil. Confirm interchangeability against your housing before ordering.
Media & Frame
Product photography for IAS-DC-PANEL-2424 is in preparation. Construction and dimensional detail are fully specified in the table below.
- Synthetic polyester media, uniform radial pleat
- Welded-wire media-support grid
- High wet-strength beverage-board enclosing frame

Complete Technical Specifications
| Parameter | 2 in. Depth | 4 in. Depth |
|---|---|---|
| — Dimensions — | ||
| Nominal size | 24 × 24 × 2 in. (610×610×51 mm) | 24 × 24 × 4 in. (610×610×102 mm) |
| Actual depth | 1.75 in. (44.5 mm) | 3.75 in. (95.3 mm) |
| Actual face | 23.38 × 23.38 in. | 23.38 × 23.38 in. |
| — Performance — | ||
| Airflow capacity | 2,000 cfm (≈3,400 m³/h) | 2,000 cfm (≈3,400 m³/h) |
| Initial resistance | 0.31 in. w.g. (≈77 Pa) | 0.27 in. w.g. (≈67 Pa) |
| Recommended final resistance | 1.0 in. w.g. (≈249 Pa) | 1.0 in. w.g. (≈249 Pa) |
| Media area | 17 sq ft | 28 sq ft |
| Efficiency rating | MERV 8, MERV-A 8 per ASHRAE 52.2 with Appendix J; ISO 16890 ePM10-50% | |
| — Media & construction — | ||
| Media | Synthetic polyester blend, uniform radial pleat | |
| Media support | Welded-wire grid | |
| Frame | High wet-strength beverage board | |
| — Listing & limits — | ||
| Listing | UL Class 900 | |
| Max. operating temperature | 200 °F (93 °C) | |
Metric values are conversions of the US customary specification. Specification values are those published for the Camfil Farr 30/30 reference product (see cross-reference above); Iodine Air Systems' own factory test reports are confirmed at quotation.
Applications
- Outdoor-air intake prefiltration ahead of a MERV 13-15 final filter
- Makeup-air unit prefiltration
- Coil protection — captures coarse dust before it reaches the cooling coil
- General-purpose data center HVAC prefiltration where MERV 8 room-air filtration is the design point
For the downstream final-filter stage, see IAS-DC-RIGID-2424 (rigid box, MERV 13/14) or IAS-DC-VBANK-2424 (V-bank, MERV 14/15).
Questions about IAS-DC-PANEL-2424
Is IAS-DC-PANEL-2424 a replacement for Camfil Farr 30/30?
It is built to the same published dimensional and performance specification as Camfil Farr 30/30 in 24 × 24 × 2 in. and 24 × 24 × 4 in.: 2,000 cfm airflow capacity, 0.31 in. w.g. / 0.27 in. w.g. initial resistance, and MERV 8 per ASHRAE 52.2. It is an Iodine Air Systems product, not a Camfil product, and we are not affiliated with Camfil. Confirm interchangeability against your housing before ordering.
Should I order the 2 in. or the 4 in. depth?
Both depths are rated for the same 2,000 cfm in this face size, but the 4 in. depth carries more media area (28 sq ft vs. 17 sq ft) at a lower initial resistance (0.27 in. w.g. vs. 0.31 in. w.g.), which generally means a longer service interval before reaching the recommended 1.0 in. w.g. final resistance. Choose the depth that fits your existing holding frame or housing.
Is this a final filter or a prefilter?
IAS-DC-PANEL-2424 is a prefilter. ASHRAE Technical Committee 9.9's own guidance describes MERV 8 as the room-air filtration level and MERV 11 or preferably MERV 13 for air entering a data center, so this MERV 8 panel is normally staged ahead of a MERV 13-15 final filter such as IAS-DC-RIGID-2424 or IAS-DC-VBANK-2424, not used alone as the only filtration stage on outdoor air.
What does the recommended final resistance mean?
1.0 in. w.g. is the manufacturer-published recommended changeout point for this filter family at this depth. Your building management system or a manometer on the filter bank tracks differential pressure against that figure; system design may dictate a different changeout point for your installation.
How do I order?
Email sales@iodineairsystems.com with the part number (depth), quantity, delivery destination, Incoterm (FOB or CIF), and your required date. Pricing and lead time are confirmed in the quotation.